31
INSTALLERUSER
MAINTENANCE TECHNICIAN
d9
- Maximum temperature in tank 1.
TkM1” parameter (default value
“65°C”).
- Maximum value of the desired tem-
perature of the water in tank 1 dur-
ing normal operation. (Adjustable
between +15 and 95°C with default
value 65°C).
- Maximum delta temperature for tank
1
dtM1” parameter (default value
“15°C”).
- Dierence between temperature T1
of the manifold and temperature
T2 of tank 1 to activate main pump
1. (Adjustable between 3 and 40°C
with recommended temperature
7°C).
- Minimum delta temperature for
tank 1.
dtm1” parameter (default value
“7°C”).
- Dierence between temperature T1
of the manifold and temperature
T2 of tank 1 to stop main pump 1.
(Adjustable between 2 and (tank.1
dTMax -2°C) with recommended
temperature 3°C).
- Minimum manifold temperature.
mtCo” parameter (default value
“25°C”).
- is setting is used to dene a min-
imum temperature on the manifold,
to authorise the solar charge. (Ad-
justable between 0°C and 99°C with
default value 25°C).
1.16 ANTIFREEZE
PROTECTION.
Assembly instructions.
- Wind the heating cable (d9) around
the connection pipes and safety valve.
Attention: the graphic representation
of the heating cable is purely indicative.
Minimum temperature -5°C. The
pack comes standard with an antifreeze
function that activates the electric re-
sistance when the temperature in the
Solar Container falls below 4°C.
e antifreeze function is only guar-
anteed if:
- the pack is connected properly to the
electrical circuit and is constantly
powered;
- the essential components are not
faulty.
In these conditions the pack is protected
against freezing up to an ambient tem-
perature of -5°C.
38