5-6 Selecting Functions
5
Min. Factory
Name Setting range unit setting
P01 Number of motor 1 2 to 14 2 4 X 0
poles
P02 Motor1 (Capacity) 0.01 to 5.5kW (4.0kW or less)
Nominal
0.01 to 11.00kW(5.5/7.5kW) 0.01kW
applied
X4
motor kW
P03 (Rated current) 0.00 to 99.9A 0.01A
standard
X6
rating
P04
_
Tuning) 0: Inactive
1: Active (%R1, %X)
2: Active (%R1, %X, Io) 1 0 X 12
P05 (Online tuning) 0: Inactive
1: Active 1 0 X 0
P06 (No-load current) 0.00 to 99.9A 0.01A
standard
X6
rating
P07
_
R1 setting
_
0.00 to 50.00% 0.01%
standard
4
rating
P08
_
X setting
_
0.00 to 50.00% 0.01%
standard
4
rating
P09 (Slip compensation 0.00 to 15.00Hz 0.01Hz 0.00 4
control 1)
P10 (Slip compensation 0.01 to 10.00s 0.01s 0.50 4
response time 1)
Function code
Change during
operation
RS485 Data format
User setting
P: Motor parameters
Description of change during operation
: The data changed by the or key takes
effect on the inverter operation. However,
press the key to store the new data.
V
V
: Press the or key to change the data.
The new data takes effect after the key is
pressed to store the data.
X : The data can be changed only while the
inverter is stopped.
V
V
FUNC
DATA
FUNC
DATA

Table of Contents