Programming Manual
70 Operating the system
Chapter 28
Operating the system
Only persons responsible for the safety of the building and its occupants (Level 2) can operate the
system after entering a code or inserting the key in the keyswitch.
These operators can access the functions described in this chapter.
28.1 Change Day/Night mode
FROM COMPUTER
Not available.
This option will allow operators to change the Day/Night operating mode manually.
FROM PANEL
<any key>, 3 Panel Settings, <code>, panel in Mode,
or <any key>, 3 <code> /
Press keys and to change the
function mode.
Note: For automatic control of the Day/Night mode function, ypu must set up a timer.
28.2 Bypassing a device
FROM COMPUTER
Not available.
Under certain circumstances (e.g. maintenance or fault conditions), it may be necessary to bypass a
zone or a point. Bypassed zones or points cannot generate fault or alarm signals and cannot be
activated.
FROM PANEL
<any key>, 4 Disable, <code>, 1 Loop devices, x Loop x, yyy point,
or <any key>, 4 <code> 1 x yyy
Press ESC to confirm and step back to
the previous menu.
28.3 Bypassing a zone
FROM COMPUTER
Not available.
During maintenance or fault status, it may become necessary to bypass a zone. Bypassed zones
cannot generate faults, alarms or signals and cannot be activated.
panel in Mode : _ay
Point x/yyy <Dev. Description>
< Device Type >
STATUS : _nabled
= Select Point = Enable/Disable

Table of Contents

Other manuals for INIM Electronics SmartLoop

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INIM Electronics SmartLoop and is the answer not in the manual?

INIM Electronics SmartLoop Specifications

General IconGeneral
BrandINIM Electronics
ModelSmartLoop
CategoryControl Panel
LanguageEnglish

Related product manuals