7 PLC programming
49
D8419
Temperature detection 2 channel average filter constant. The default
value is 8.
AD offset
gain
setting
M8420
Setting 1 writes the AD offset gain value. It will automatically return to 0
after writing.
D8420
0x6A1 means 6AT station card. Displaying 0x6A2 means 6ATC
expansion card.
D8421
AD1 offset
D8422
AD1 gain
D8423
AD offset
D8424
AD2 gain
DA offset
gain
setting
M8430
Set 1 to write the DA offset gain value. It will automatically return to 0
after writing.
D8430
0x6A1 means 6AT station card. Display 0x6A2 means 6ATC expansion
card
D8431
DA1 offset
D8432
DA 1 gain
D8433
DA 2 offset
D8434
DA 2 gain
M8440
Clear the temperature detection disconnection mark.
AD error status is shown in the table below
D8403 (AD
sampling error)
ON state
OFF state
Bit 0
There is an error, and any non-zero A/D
conversion of Bit 0~Bit 3 will stop
No error
Bit 1
Wrong offset/gain setting
Offset/gain correct
Bit 3
Hardware malfunction
Hardware is normal
Bit 4
Number is outside the range of -2048 to 2047
Digital output is normal
Bit 5
Sampling filter constant exceeds the range of
1 to 4096
Sampling filter constant
is normal
Bit 15
AD parameter initialization is unsuccessful,
need to set M8420 to reinitialize
AD parameter
initialization is normal
DA error status is shown in the table below
D8406 (DA
sampling error)
ON state
OFF state
Bit 0
If there is an error, any non-zero D/A
conversion of Bit 0Bit 3 will stop
No error
Bit 1
Wrong offset/gain setting
Offset/gain correct
Bit 3
hardware malfunction
The hardware is normal
Bit 4
The number exceeds the range of -2350 ~
2350
Digital output is normal
Bit 15
DA parameter initialization is unsuccessful,
need to set M8420 to reinitialize
DA parameter
initialization is normal