7 PLC programming
50
The temperature detection error status is shown in the table below
D8409 (temperature
detection error)
ON state
OFF state
Bit0
There is an error, and any non-zero A/D
conversion of Bit0Bit3 will stop
No error
Bit3
Hardware malfunction
The hardware is
normal
Bit4
Digital output out of range
Digital output is
normal
Bit5
The sampling filter constant exceeds the
range of 1 to 256
Sampling filter
constant is normal
Bit8
The temperature of the first channel is
lower than the measurable temperature
Normal temperature
Bit9
The temperature of the first channel is too
high or disconnected
Normal temperature
Bit10
The second channel temperature is lower
than the measurable temperature
Normal temperature
Bit11
The second channel temperature is too
high, or disconnected
Normal temperature