Err14
If the ambient temperature is too high
If the air duct is blocked
If the fan is broken
Reduce the ambient
temperature
Clear the air duct
Replace the fan
Module overheating
Yes
Yes
Yes
If the thermal resistor of the module broken
Replace the thermal
resistor
Ask for technical support
Yes
No
No
No
If the driver module is broken
Replace the driver
module
Yes
No
Module Overheating (Err14)
External Equipment Fault (Err15)