- 122 -
Function
Code
Name LED Display Setting Range Min. Unit Default Property
FD-01
Data format Data format 0: No check, data format
<8,N,2>
1: Even parity check, data
format <8,E,1>
2: Odd Parity check, data
format <8,O,0>
1 0
☆
FD-02 Local address Local address 0: Broadcast address
1 to 247
1 1
☆
FD-03 Response delay Response delay 0 to 20 ms 1 2 ms
☆
FD-04 Timeout duration Timeout duration 0.0s: Invalid
0.1s to 60.0s
0.1s 0.0s
☆
FD-05 Communication
protocol
Communication protocol 0: Standard Modbus
protocol, used for host
computer parameter
reading/writing and running
control
1: Inovance private protocol,
used for communication with
background oscilloscope
1 1
☆
Group FP: User Password
FP-00 User password User password 0–65535 1 0
☆
FP-01 Parameter initialization Parameter initialization 0: No operation
1: Restore default settings
2: Clear fault records
3: Restore user parameters
4: Restore system factory
parameters except A2-01
5: Restore default settings
of all parameters (except
groups FF, FP and FA,
remember to back up the
parameters)
1 0
☆
FP-02 Motor model Motor model 0 to 65535 1 0
☆
FP-03 Reserved - - - - -
FP-04 Password for user
storage operation
Password for user
storage operation
0 to 65535 1 0
☆
FP-05 User storage mode User storage mode 0: No operation
1: Store user parameters
1 0
☆
FP-06 Equipment
specications displayed
on operation panel
Equipment
specications displayed
on operation panel
in both Chinese and
English
0 to 65535 1 0
☆