Chapter 3 Mechanical and Electrical Installation IS580 User Manual
- 20 -
Chapter 3 Mechanical and Electrical Installation
3.1 Mechanical Installation
3.1.1 Installation Environment
Item Requirements
Ambient temperature -10°C to 50°C
Heat dissipation Install the servo drive on an incombustible supporting surface and make sure there is sufcient
space around the enclosure to allow for efcient heat dissipation. Use strong screws or bolts to
secure the enclosure on the supporting surface.
Mounting location Make sure the mounting location is:
Away from direct sunlight
Not in an area that has high humidity or condensation
Protected against corrosive, combustible or explosive gases and vapours
Free from oil, dirt, dust or metallic powders.
Vibration Make sure the mounting location is not affected by levels of vibration that exceed 0.6 g.
Avoid installing the enclosure near to punching machines or other mechanical
machinery that generates high levels of vibration or mechanical shock.
3.1.2 Mounting Orientation and Clearance
Mounting Clearance
The mechanical clearance requirements for the IS580 vary with power classes of the servo drive.
Figure 3-1 Mounting clearance of the IS580
The servo drive shall be installed
vertically upward.
C
B
A
A
IS580
Hot air
Cold air
IS580T020-R1-1 to IS580T040-R1-1
A 10
IS580T050-R1-1 to IS580T070-R1-1
A 50
IS580T080-R1-1
to IS580T210-R1-1
A
50
Installation clearance requirements on the IS580 series servo
drives of different power classes
Power Class Clearance Requirements (Unit: mm)
B 200
B 200
B
300
Minimum air duct area for a servo drive
(If N servo drives are required, enlarge the air duct area by N times.)
IS580T020-R1-1 to IS580T040-R1-1
IS580T050-R1-1 to IS580T070-R1-1
IS580T080-R1-1 to IS580T100-R1-1
Power Class
19200
30400
48400
78600
IS580T140-R1-1 to IS580T210-R1-1
Minimum Air Duct Area (mm²)
IS580T080-R1
-H-1 to IS580T210-R1-H-1
A 80
B 200
B 200
B 200
B 300
B 20
33800
IS580T140-R1-H-1 to IS580T210-R1-H-1