Description of Function Codes
MD280 User Manual
- 110 -
source, PID feedback source, and reference 0 in the multi-reference function.
 When the pulse frequency for the counter input and length counting input is high, use
DI5; otherwise, use DI1 to DI4.
Function Code Parameter Name Default
F2-00 DI1 function selection )RUZDUG581):'
F2-01 DI2 function selection 5HYHUVH5815(9
F2-02 DI3 function selection )RUZDUG-2*)-2*
F2-03 DI4 function selection 8: Coast to stop
F2-04 DI5 function selection 0: No function
7KHIROORZLQJWDEOHOLVWVWKHIXQFWLRQVDYDLODEOHIRUWKH',WHUPLQDOV1RWHWKDWH[FHSWIXQFWLRQ
0, the same function must not be allocated to multiple DI terminals. If a function cannot
be selected, check whether this function has been allocated to other terminals, or is being
used.
Table 6-2 Functions of DI terminals
Value Function Description
0 No function Set 0 for reserved terminals to avoid malfunction.
1 )RUZDUG581):'
:KHQ)LVVHWWR7HUPLQDOFRQWUROWKHWHUPLQDOVDUH
used to control forward or reverse RUN of the AC drive.
For details, see the description of F2-06.
2 5HYHUVH5815(9
3 Three-line control
4 )RUZDUG-2*)-2* FJOG indicates forward JOG running, while RJOG indicates
reverse JOG running. The JOG frequency, acceleration time
and deceleration time are described respectively in F5-00,
F5-01 and F5-02.
5
Reverse JOG
5-2*
6 Terminal UP
:KHQ)LVVHWWR'LJLWDOVHWWLQJWKHWHUPLQDOVZLWK
the two functions are used as increment and decrement
FRPPDQGVIRUIUHTXHQF\PRGL¿FDWLRQ7KHWHUPLQDO83
DOWN rate is determined in F2-07.
7 Terminal DOWN
8 Coast to stop
When the terminal with this function becomes ON, the AC
drive blocks its output, and the motor coasts to rest and is
not controlled by the AC drive.
9 )DXOWUHVHW5(6(7
The terminal is used for fault reset function, the same as the
function of RESET key on the operation panel. This function
is implemented by pulse input.
10 RUN pause
When the terminal with this function becomes ON, the AC
drive stops in the mode set in F4-10. If the PLC controls the
AC drive at this time, the PLC memorizes the frequency and
running time at the pause moment and does not count the
pause time.