MD280 User Manual Description of Function Codes
- 113 -
SUHFHGHQFHRYHUIXQFWLRQ&RPPDQGVRXUFHVZLWFKRYHUWRWHUPLQDOFRQWURO:KHQ
either of the two functions is valid, the function of switchover between operation panel
control and remote command channel provided by the
MF.K
key is disabled.
Motor 2 parameters are set in group FC; the V/F curve of motor 2 is straight line by
default; the acceleration/deceleration time is set in FC-09.
The three multi-reference terminals have 16 state combinations, corresponding to eight
reference values, as listed in the following table.
Table 6-3 State combinations of the four multi-reference terminals
K3 K2 K1 Reference Setting Corresponding Parameter
OFF OFF OFF Reference 0 F8-00
OFF OFF ON Reference 1 F8-01
OFF ON OFF Reference 2 F8-02
OFF ON ON Reference 3 F8-03
ON OFF OFF Reference 4 F8-04
ON OFF ON Reference 5 F8-05
ON ON OFF Reference 6 F8-06
ON ON ON Reference 7 F8-07
Function Code Parameter Name Setting Range Default
F2-05 ',¿OWHUWLPH 0–10 4
It is used to set the software filter time of DI terminal status. If DI terminals are liable to
interference and may cause malfunction, increase the value of this parameter to enhance
WKHDQWLLQWHUIHUHQFHFDSDELOLW\+RZHYHULQFUHDVHRI',¿OWHUWLPHZLOOUHGXFHWKHUHVSRQVH
of DI terminals.
Function Code Parameter Name Setting Range Default
F2-06 Terminal command mode
0: Two-line mode 1
1: Two-line mode 2
2: Three-line mode 1
3: Three-line mode 2
0
7KLVSDUDPHWHULVXVHGWRVHWWKH PRGHLQZKLFKWKH$&GULYHLVFRQWUROOHGE\H[WHUQDO
WHUPLQDOV7KHIROORZLQJXVHV',', DQG',DPRQJ',WR',DV DQH[DPSOHZLWK
allocating functions of DI1, DI2 and DI3 by setting F2-00 to F4-02.
0: Two-line mode 1
It is the most commonly used two-line mode, in which the forward/reverse rotation of
the motor is decided by DI1 and DI2. The parameters are set as below:
Function Code Parameter Name Value Function Description
F2-06 Terminal command mode 0 Two-line 1
F2-00 DI1 function selection 1 )RUZDUG581):'
F2-01 DI2 function selection 2 5HYHUVH5815(9