Description of Function Codes
MD280 User Manual
- 126 -
Figure 6-12 S-curve acceleration/deceleration A
Output
frequency Hz
Set frequency f
Time t
t1 t2 t2t1
Figure 6-13 S-curve acceleration/deceleration B
Output
frequency Hz
Set frequency f
Rated frequency fb
T
Time t
Function Code Parameter Name Setting Range Default
F4-10 Stop mode
0: Decelerate to stop
1: Coast to stop
0
 0: Decelerate to stop
After the stop command is enabled, the AC drive decreases the output frequency
according to the deceleration time and stops when the frequency decreases to zero.
 1: Coast to stop
After the stop command is enabled, the AC drive immediately stops the output. The
motor will coast to stop based on the mechanical inertia.
Function Code Parameter Name Setting Range Default
F4-11 Initial frequency of stop DC braking
+]WRPD[LPXP
IUHTXHQF\)
0.00 Hz
F4-12 Waiting time of stop DC braking 0.0–36.0s 0.0s
F4-13 Stop DC braking current 0%–100% 0%
F4-14 Stop DC braking time 0.0–36.0s 0.0s
 ),QLWLDOIUHTXHQF\RIVWRS'&EUDNLQJ
During the process of decelerating to stop, the AC drive starts DC braking when the
running frequency is lower than the value set in F4-11.