MD280 User Manual Description of Function Codes
- 133 -
When the dormant function is enabled, if the frequency source is PID, whether PID
operation is performed in the dormant state is determined by F6-10. In this case, select PID
RSHUDWLRQHQDEOHGLQWKHVWRSVWDWH)
Function Code Parameter Name Setting Range Default
F5-25
Software overcurrent
threshold
±UDWHGPRWRUFXUUHQW 200.0%
F5-26
Software overcurrent
detection delay
VQRGHWHFWLRQ
0.01–6500.0s
0.0s
If the output current of the AC drive reaches the overcurrent threshold and the duration
H[FHHGVWKHGHWHFWLRQGHOD\WLPHWKH$&GULYHUHSRUWV(55
Function Code Parameter Name Setting Range Default
F5-27
Overcurrent detection delay
IRU'2RXWSXW
VQRGHWHFWLRQ
0.01–6500.0s
0.00s
If the output current of the AC drive reaches the overcurrent threshold and the duration
H[FHHGVWKHGHWHFWLRQGHOD\WLPHWKH'2WHUPLQDOZLWKIXQFWLRQEHFRPHV21
Function Code Parameter Name Setting Range Default
F5-37 Dead zone compensation
0: Disabled
1: Enabled
1
If the frequency is lower than 200 Hz, set this parameter to 0; otherwise, set this parameter
to 1.
Function Code Parameter Name Setting Range Default
F5-38 Cooling fan control
0: Fan working during running
1: Fan working continuously after
power-on
0
Function Code Parameter Name Setting Range Default
F5-39
([WHUQDOEUDNLQJVWDUWXS
frequency
+]WRPD[LPXPIUHTXHQF\
)
0.00 Hz
F5-40 ([WHUQDOEUDNLQJWLPH 0.0–3600.0s 0.0s
At stop, when the running frequency is lower than the value of F5-39, the braking signal is
active. The braking signal becomes invalid after lasting the time set in F5-40.
The braking signal is inactive during startup.
Function Code Parameter Name Setting Range Default
F5-41
Jump frequency
H[HFXWLRQPRGH
1RWH[HFXWHGXULQJDFFHOHUDWLRQ
deceleration
([HFXWHGXULQJDFFHOHUDWLRQ
deceleration
0
Function Code Parameter Name Setting Range Default
F5-43 3RZHURQWLPHLQVHFRQG 0.00–3599s 0s