Mechanical and Electrical Installation MD280 User Manual
- 48 -
Type Terminal Name Function Description
Digital
input
DI1-COM Digital input 1
Optical coupling isolation
,QSXWLPSHGDQFHNȍ
DI2-COM Digital input 2
DI3-COM Digital input 3
DI4-COM Digital input 4
DI5-COM
High-speed
pulse input
Optical coupling isolation
,QSXWLPSHGDQFHNȍ
High-speed pulse input
0D[LPXPLQSXWIUHTXHQF\N+]
Analog
output
AO-GND Analog output 1
Voltage or current output is decided by jumper
J3.
Output voltage range: 0–10 V
Output current range: 0–20 mA
Digital
output
DO1-COM
DO2-COM
Digital output
:KHQSRZHUHGE\H[WHUQDOSRZHUVXSSO\VKRUW
24V and EXT via jumper J7; when powered
by internal power supply: short 24V and IN via
jumper J7.
Optical coupling isolation, open-collector output
Output voltage range: 0–24 V
Output current range: 0–50 mA
FM- COM
High-speed
pulse output
,WLVOLPLWHGE\))0WHUPLQDORXWSXWPRGH
VHOHFWLRQ
$VKLJKVSHHGSXOVHRXWSXWWKHPD[LPXP
frequency hits 50 kHz.
$VRSHQFROOHFWRURXWSXWLWVVSHFL¿FDWLRQLVWKH
same as that of DO1
FM terminal can be selected as AO, FM or DO3
output.
Relay
output
T/A-T/B NC terminal
Contact driving capacity:
9$&$&26¡
30 VDC, 1 A
T/A-T/C NO terminal
$X[LOLDU\
interface
$$
RS485
communication
port
It is the standard RS485
Keypad
([WHUQDO
operation panel
interface
It is the standard RJ45 network cable interface
DQGFRQQHFWVWKHH[WHUQDORSHUDWLRQSDQHO
efesotomasyon.com