MD280 User Manual Function Code Table
- 81 -
Function
Code
Parameter Name Setting Range
Min.
Unit
Default
Property
F2-03
DI4 function
selection
30: Command source
switchover to operation panel
control
31: Command source
switchover to terminal control
32: Motor switchover
33: Frequency source
switchover
34: Lock running frequency
35: Select main frequency
source
6HOHFWDX[LOLDU\IUHTXHQF\
source
37: Motor switchover during
running
(QG
18
ƾ
F2-04
DI5 function
selection
10
ƾ
F2-05 ',¿OWHUWLPH 0–10 1 4
ƿ
F2-06
Terminal command
mode
0: Two-line mode 1
1: Two-line mode 2
2: Three-line mode 1
3: Three-line mode 2
10
ƾ
F2-07
Terminal UP/
DOWN rate
0.01–100.00 Hz/s
0.01 Hz/
s
1.00 Hz/s
ƿ
F2-08 AI1 minimum input 0.00 V to F2-10 0.01 V 0.02 V
ƿ
F2-09
Corresponding
setting of AI1
minimum input
-100.00%–100.0% 0.1% 0.0%
ƿ
F2-10 $,PD[LPXPLQSXW F2-08 to 10.00 V 0.01 V 10.00 V
ƿ
F2-11
Corresponding
setting mode of AI1
PD[LPXPLQSXW
0: F2-12
1: Determined by AI2
10
ƾ
F2-12
Corresponding
setting of AI1
PD[LPXPLQSXW
-100.00%–100.0% 0.1% 100.0%
ƿ
F2-13 $,¿OWHUWLPH 0.00–10.00s 0.01s 0.10s
ƿ
F2-14 AI2 minimum input 0.00 V to F2-16 0.01 V 0.02 V
ƿ
F2-15
Corresponding
setting of AI2
minimum input
-100.00%–100.0% 0.1% 0.0%
ƿ
F2-16 $,PD[LPXPLQSXW F2-14 to 10.00 V 0.01 V 10.00 V
ƿ