Chapter 3 Mechanical and Electrical Installation 
 
-33- 
 
4. Main Circuit Terminals and Connections 
Danger Danger 
1) The wiring operation is enabled only after confirming that the power switch is OFF.  
Otherwise, electric shock may be caused! 
2) The wiring operation can only be performed by professional technicians. Otherwise, it 
may cause harm to equipment and human!
 
    Reliable grounding is required. Otherwise, it may cause electric shock or fire! 
Danger Danger 
1) Confirm that the input power is consistent with the rating of inverter. Otherwise, the 
inverter may be damaged!
 
2) Confirm whether the motor adapts to the inverter. Otherwise, the motor may be 
damaged or inverter protection may arise!
 
3) Don’t connect power supply to U, V and W terminal. Otherwise, the inverter may be 
damaged!
 
4) Do not directly connect the brake resistor between the DC bus terminals (+) and (-). 
Otherwise, it may cause fire! 
 
  1) Instructions of main circuit terminals of single-phase inverter:   
Terminals  Name  Description 
L1 and L2 
Input terminal of 
single-phase power supply 
AC single-phase 220V power 
connection point 
(+)ǃ(-) 
Negative and positive 
terminals of DC bus 
Shared DC Bus input point 
(+) and PB 
Connecting terminal of brake 
resistor  
Connect the brake resistor 
U, V and W  Output terminal of inverter  Connect the three-phase motor 
 
Earth terminal 
Earth terminal 
2) Description of main circuit terminals of three-phase inverter 
Terminals  Name  Description 
R, S and T 
  Input terminal of three-phase 
power supply 
AC three-phase 380V power 
connection point 
(+)ǃ(-) 
Negative and positive 
Shared DC Bus input point 
 