Chapter 3 Mechanical and Electrical Installation 
 
-36- 
 
3) Wiring of control terminal:   
  A. Analog input terminal:   
 Generally, it is required to use shielding 
cable and the wiring distance shall be as 
shorter as possible (not longer than 20m), as 
the weak analog signal is especially prone to 
the external interference. As shown in the 
following figure:   
Less than 20 Meters
Potentiometer
Fig.3-9 Schematic Diagram for Connection of      
Input Terminal of Analog SignalIf there is 
severe interference in the analog signal, filter 
capacitor or ferrite magnetic ring shall be 
added to the analog signal side. As shown in 
Fig.3-10  Wiring diagram for adding filter to 
analog input terminal
 
Cross in the Same Direction or Wind
2 to 3 Coils in the Same Direction
 External Analog
Source
Ferrite Magnetic Ring
 
Fig.3-10    Wiring diagram for adding filter to 
analog input terminal 
B. Digital input terminal:   
    The ON/OFF statuses of these terminals 
are judged by the received digital signal of 
inverter. Hence, the external contact shall be 
the connection point with high reliability for 
conducting weak signal.   
If the ON/OFF signals to the digital input 
terminal of inverter are provided by open 
collector output, it is necessary to take the 
error acts caused by power interference into 
consideration.    It is recommended to use the 
contact control mode.   
C. Digital output terminal:   
When the digital output terminal needs 
the drive relay, absorption diode shall be 
installed at the two sides of the relay coil.  
Otherwise it may damage DC 24 power 
supply easily.   
Note: The absorption diode shall be 
installed with correct polarity, as shown in 
Fig.3-11. as shown the following figure.  
Otherwise, when there the digital output 
terminal has output, the DC 24V power supply 
and output circuit will be damaged 
immediately.  
Relay
 Diode
 
 
Fig.3-11 Schematic diagram for connection 
of digital output terminal     
 
 
 
 