Chapter 3 Mechanical and Electrical Installation 
 
-35- 
 
2. Description of Control Terminal Function:   
Type 
Terminal 
Symbol 
Terminal 
name 
Function description 
+10V-GND 
External 10V 
power supply
Provide +10V power supply for external units, 
and the maximum output current is 10mA.   
It is generally used as the operating power of 
external potentiometer. 
Power 
supply 
+24V-COM 
External 24V 
power supply
Provide +24V power supply for external units. It 
is generally used as the operating power supply 
for digital input/output terminal and the external 
sensor.  
The maximum output current is 200mA.   
AI1-GND 
Analog input 
terminal 1 
1 Input Voltage range: DC 0V to 10V 
2. Input resistance: 100kȍ 
Analog 
input 
AI2-GND 
Analog input 
terminal 2 
1. Input range: DC 0V to 10V/4mA to 20mA, 
which is determined by j3 jumper on the 
control board.   
2. Input impedance: It is 100kȍ at the time of 
voltage input and 500ȍ at the time of current 
input.  
DI1  Digital input 1
DI2  Digital input 2
DI3  Digital input 3
2. Input impedance: 3.3kȍ 
Function  
Digital 
input 
terminal 
 
DI4 
High-speed 
pulse input 
terminal 
In addition to the characteristics of DI1 to DI3, 
DI4 can also be used as the high-speed pulse 
input channel.   
Maximum input frequency is 50kHz. 
Analog 
output 
AO-GND 
Analog 
output 
The voltage or current output is determined by 
the J4 jumper on the control board.   
Digital 
output 
DO-COM 
Digital output 
1 
Output voltage range: 0V to 24V 
Output current range: 0mA to 50mA 
T/A-T/B 
normally 
closed 
terminal 
Relay 
output 
T/A-T/C 
normally 
open terminal
Contact driving capacity:   
AC250Vˈ3AˈCOSij=0.4 
DC 30Vˈ1A 
 
efesotomasyon.com