Chapter 5 Function Parameter Table
-45-
Code Name Setup range
Minimum
unit
Factory
default
value
Cha-
nge
F1-09
Mutual inductive
reactance
0.01mH655.35mH
0.1 mH
model
dependent
ż
F1-10 No-load current
0.0A650.00A
0.01A
model
dependent
ż
F1-11 Tuning selection
0: no operation
1: static tuning
2. Complete tuning
1 0 ×
Group F2 Vector and VF Control Parameters
F2-00
Vector control
speed loop
proportion gain 1
1100
1 30 ż
F2-01
Vector control
speed loop
integration time 1
0.01s 10.00s
0.01s 0.50s
ż
F2-02
Vector control PI
parameter switch
frequency 1
0.00 F2-05
0.01Hz 5.00Hz
ż
F2-03
Vector control
speed loop
proportion gain 2
1100
1 25 ż
F2-04
Vector control
speed loop
integration time 2
0.01s 10.00s
0.01s
1.00 ż
F2-05
Vector control PI
parameter switch
frequency 2
F2-0250.00Hz
0.01Hz 10.00Hz
ż
F2-06
Vector control slip
compensation
factor
50%200%
1% 100% ż
F2-07
Vector control
speed loop filter
time / VF control
AVR selection
0.000s 0.100s
0.001s 0.002s
ż