Chapter 5 Function Parameter Table
-48-
Code Name Setup range
Minimum
unit
Factory
default
value
Cha-
nge
F5-04
Stall gain over
current
0(no stall over voltage) 100
1 20 ż
F5-05
Stall point over
current
100%200%
1% 150% ż
F5-06
Fault auto reset
times
03
1 0 ż
F5-07
Fault auto reset
interval J
0.1s to 100.0s 0.1s 1.0s
ż
F5-08
Input phase loss
protection
selection
0: Disabled
1: Enabled
1 1 ż
F5-09
Inverter load lost
protection
selection
0: Disabled
1: Enabled
1 1 ×