Function Code Table
MD380 User Manual
- 124 -
)unction
Code
Parameter Name
Setting Range
Default Property
A3-53
To
rque adjustment
proportional gain
0–20000
2000 ƿ
A3-54
To
rque adjustment integral
gain
0–20000
1300 ƿ
A3-55 Speed loop integral property
Unit's digit: Integral separated
0: Disabled
1: Enabled
0 ƿ
A3-56
)ield weakening mode of
synchronous motor
1R¿HOGZHDNHQLQJ
1: Direct calculation
2: Adjustment
0 ƿ
A3-57
)ield weakening degree of
synchronous motor
50%–500%
100% ƿ
A3-58
Maximum ¿eld weakening
current
1%–300%
50% ƿ
A3-59
)ield weakening automatic
adjustment gain
10%–500%
100% ƿ
A3-60
)ield weakening integral
multiple
2–10
2 ƿ
A3-61 Motor 2 control mode
6HQVRUOHVVÀX[YHFWRUFRQWURO
6)9&
1: Closed-loop vector control
(CLVC)
9ROWDJH)UHTXHQF\9)
control
0 ƿ
A3-62
Motor 2 acceleration/
deceleration time
0: Same as motor 1
1: Acceleration/Deceleration time 1
2: Acceleration/Deceleration time 2
3: Acceleration/Deceleration time 3
4: Acceleration/Deceleration time 4
0 ƿ
A3-63 Motor 2 torque boost
0.0%: Automatic torque boost
0.1%–30.0%
Model
dependent
ƿ
A3-65
Motor 2 oscillation
suppression gain
0–100
Model
dependent
ƿ
Group A
4: Motor 4 Parameters
A4-00 Motor type selection
0: Common asynchronous motor
1: Variable frequency
asynchronous motor
2: Permanent magnetic
synchronous motor
0 ƾ
A4-01 Rated motor power
0.1–1000.0 kW
Model
dependent
ƾ
efesotomasyon.com