MD380 User Manual Desc
ription of Function Codes
- 215 -
)LJXUH5HDFKLQJWKHVHWFRXQWYDOXHDQGGHVLJQDWHGFRXQWYDOXH
Count pulses input
Count pulses input
Designated count
value reached output
Set count value
reached output
123
1110 12 20 2119
12
)E-09 = 11
U0-12 = 11
)E-08 = 20
U0-12 = 20
U0-12 = 0
U0-12: Count value
Group )C: Multi-Reference and Simple PLC )unction
7KH0'PXOWLUHIHUHQFHKDVPDQ\IXQFWLRQV%HVLGHVPXOWLVSHHGLWFDQEHXVHGDVWKH
VHWWLQJVRXUFHRIWKH9)VHSDUDWHGYROWDJHVRXUFHDQGVHWWLQJVRXUFHRISURFHVV3,',Q
addition, the multi-reference is relative value.
The simple PLC function is different from the MD380 user programmable function. Simple
PLC can only complete simple combination of multi-reference, while the user programmable
IXQFWLRQLVPRUHSUDFWLFDO)RUGHWDLOVVHHWKHGHVFULSWLRQVRIJURXS$
)unction Code Parameter Name Setting Range Default
)C-00 Reference 0 -100.0%–100.0% 0.0%
)C-01 Reference 1 -100.0%–100.0% 0.0%
)C-02 Reference 2 -100.0%–100.0% 0.0%
)C-03 Reference 3 -100.0%–100.0% 0.0%
)C-04 Reference 4 -100.0%–100.0% 0.0%
)C-05 Reference 5 -100.0%–100.0% 0.0%
)C-06 Reference 6 -100.0%–100.0% 0.0%
)C-07 Reference 7 -100.0%–100.0% 0.0%
)C-08 Reference 8 -100.0%–100.0% 0.0%
)C-09 Reference 9 -100.0%–100.0% 0.0%
)C-10 Reference 10 -100.0%–100.0% 0.0%
)C-11 Reference 11 -100.0%–100.0% 0.0%
)C-12 Reference 12 -100.0%–100.0% 0.0%
)C-13 Reference 13 -100.0%–100.0% 0.0%
)C-14 Reference 14 -100.0%–100.0% 0.0%
)C-15 Reference 15 -100.0%–100.0% 0.0%
0XOWLUHIHUHQFHFDQEHWKHVHWWLQJVRXUFHRIIUHTXHQF\9)VHSDUDWHGYROWDJHDQGSURFHVV
PID. The multi-reference is relative value and ranges from -100.0% to 100.0%.
$VIUHTXHQF\VRXUFHLWLVDSHUFHQWDJHUHODWLYHWRWKHPD[LPXPIUHTXHQF\$V9)
separated voltage source, it is a percentage relative to the rated motor voltage. As process
PID setting source, it does not require conversion.
0XOWLUHIHUHQFHFDQEHVZLWFKHGRYHUEDVHGRQGLIIHUHQWVWDWHVRI',WHUPLQDOV)RUGHWDLOV
VHHWKHGHVFULSWLRQVRIJURXS)