AC Drive Model
Rated Output Current
(A)
AC Output Reactor Model
(Shanghai Eagtop)
MD380-7T355G 374 OCL-0490-EISH-E14U
MD380-7T400G 410 OCL-0490-EISH-E14U
MD380-7T450G 465 OCL-0530-EISH-E13U
MD380-7T500G 550 OCL-0600-EISH-E12U
7.4 Shielded Cable
7.4.1 Requirements for Shielded Cable
The shielded cable must be used to satisfy the EMC requirements of CE marking. Shielded
cables are classified into three-conductor cable and four-conductor cable. If conductivity
RIWKHFDEOHVKLHOGLVQRWVXI¿FLHQWDGGDQLQGHSHQGHQW3(FDEOHRUXVHDIRXUFRQGXFWRU
cable, of which one phase conductor is PE cable.
The
WKUHHFRQGXFWRUFDEOHDQGIRXUFRQGXFWRUFDEOHDUHVKRZQLQWKHIROORZLQJ¿JXUH
PE
Shield
PE conductor
and shield
PE
Shield
To suppress emission and conduction of the radio frequency interference effectively, the
shield of the shielded cable is cooper braid. The braided density of the cooper braid should
EHJUHDWHUWKDQ WRHQKDQFHWKHVKLHOGLQJHI¿FLHQF\DQGFRQGXFWLYLW\DVVKRZQ LQWKH
IROORZLQJ¿JXUH
Cable core
Internal insulation
Copper braidCopper shieldInsulation jacket
7KHIROORZLQJ¿JXUHVKRZVWKHJURXQGLQJPHWKRGRIWKHVKLHOGHGFDEOH
)LJXUH*URXQGLQJRIWKHVKLHOGHGFDEOH
The shield
must be
grounded.