EasyManua.ls Logo

Inovance MD380-5T5.5GB - Page 160

Inovance MD380-5T5.5GB
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MD380 User Manual Desc
ription of Function Codes
- 159 -
Set the over-excitation gain to 0 in the applications where the inertia is small and the bus
voltage will not rise during motor deceleration or where there is a braking resistor.
)unction Code Parameter Name Setting Range Default
)3-11 V/) oscillation suppression gain 0–100 Model dependent
6HWWKLVSDUDPHWHUWRDYDOXHDVVPDOODVSRVVLEOHLQWKHSUHUHTXLVLWHRIHI¿FLHQWRVFLOODWLRQ
VXSSUHVVLRQWRDYRLGLQÀXHQFHRQ9)FRQWURO
Set this parameter to 0 if the motor has no oscillation. Increase the value properly only
when the motor has obvious oscillation. The larger the value is, the better the oscillation
suppression result will be.
When the oscillation suppression function is enabled, the rated motor current and no-
ORDGFXUUHQWPXVWEHFRUUHFW2WKHUZLVHWKH9)RVFLOODWLRQVXSSUHVVLRQHIIHFWZLOOQRWEH
satisfactory.
)unction Code Parameter Name Setting Range Default
)3-13
Vo
ltage source for V/)
separation
0: Digital setting ()3-14)
1: A
I1
2: A
I2
3: AI3
4: Pulse setting (DI5)
5: Multi-reference
6: Simple PLC
7: PID
8: Communication setting
100.0% corresponds to the rated
motor voltage ()1-02, A
4-02, A5-
02, A6-02).
0
)3-14
Vo
ltage digital setting
for V/) separation
0 V to rated motor voltage 0 V
9)VHSDUDWLRQLVJHQHUDOO\DSSOLFDEOHWRVFHQDULRVVXFKDVLQGXFWLRQKHDWLQJLQYHUVHSRZHU
supply and motor torque control.
,I9)VHSDUDWHGFRQWUROLVHQDEOHGWKHRXWSXWYROWDJHFDQEHVHWLQ)RUE\PHDQVRI
analog, multi-reference, simple PLC, PID or communication. If you set the output voltage by
means of non-digital setting, 100% of the setting corresponds to the rated motor voltage. If a
negative percentage is set, its absolute value is used as the effective value.
 'LJLWDOVHWWLQJ)
7KHRXWSXWYROWDJHLVVHWGLUHFWO\LQ)
 1: AI1; 2: AI2; 3: AI3
The output voltage is set by AI terminals.
 4: Pulse setting (DI5)
The output voltage is set by pulses of the terminal DI5.
efesotomasyon.com

Table of Contents

Related product manuals