MD380 User Manual Desc
ription of Function Codes
- 165 -
,IWKHIUHTXHQF\VRXUFHLVPXOWLUHIHUHQFHWKHYDOXHRI)&WR)&FRUUHVSRQGVWR
WKHYDOXHRI)0D[LPXPIUHTXHQF\
%HVLGHVWKHPXOWLVSHHGIXQFWLRQWKHPXOWLUHIHUHQFHFDQEHDOVRXVHGDVWKH3,'VHWWLQJ
VRXUFHRUWKHYROWDJHVRXUFHIRU9)VHSDUDWLRQVDWLVI\LQJWKHUHTXLUHPHQWRQVZLWFKRYHURI
different setting values.
Two terminals for acceleration/deceleration time selection have four state combinations, as
listed in the following table.
Table 6-3 State combinations of two terminals for acceleration/deceleration time selection
Terminal 2 Terminal 1
Acceleration/Deceleration Time
Selection
Corresponding
Parameters
O)) O)) Acceleration/Deceleration time 1 )0-17, )0-18
O)) ON Acceleration/Deceleration time 2 )8-03, )8-04
ON O)) Acceleration/Deceleration time 3 )8-05, )8-06
ON ON Acceleration/Deceleration time 4 )8-07, )8-08
Two motor selection terminals have four state combinations, corresponding to four motors,
as listed in the following table.
Table 6-4 State combinations of two motor selection terminals
Terminal 2 Terminal 1 Selected Motor Corresponding Parameters
O)) O)) Motor 1 Group )1, Group )2
O)) ON Motor 2 Group A
2
ON O)) Motor 3 Group A
3
ON ON Motor 4 Group A
4
)unction Code Parameter Name Setting Range Default
)4-10 DI ¿lter time 0.000–1.000s 0.010s
It is used to set the software filter time of DI terminal status. If DI terminals are liable to
interference and may cause malfunction, increase the value of this parameter to enhance
WKHDQWLLQWHUIHUHQFHFDSDELOLW\+RZHYHULQFUHDVHRI',¿OWHUWLPHZLOOUHGXFHWKHUHVSRQVH
of DI terminals.
)unction Code Parameter Name Setting Range Default
)4-11 Te
rminal command mode
0: Tw
o-line mode 1
1: Tw
o-line mode 2
2: Three-line mode 1
3: Three-line mode 2
0
This parameter is used to set the mode in which the AC drive is controlled by external
terminals. The following uses DI1, DI2 and DI3 among DI1 to DI10 as an example, with
DOORFDWLQJIXQFWLRQVRI',',DQG',E\VHWWLQJ)WR)