MD380 User Manual Desc
ription of Function Codes
- 195 -
)unction Code Parameter Name Setting Range Default
)8-36 Output overcurrent threshold
0.0% (no detection)
0.1%–300.0% (rated
motor current)
200.0%
)8-37
Output overcurrent detection
delay time
0.00–600.00s 0.00s
If the output current of the AC drive is equal to or higher than the overcurrent threshold and
the duration exceeds the detection delay time, the corresponding DO becomes ON. The
RXWSXWRYHUFXUUHQWGHWHFWLRQIXQFWLRQLVVKRZQLQWKHIROORZLQJ¿JXUH
)LJXUH2XWSXWRYHUFXUUHQWGHWHFWLRQ
Time
Time
Output
current
Output overcurrent
threshold
)8-36
Output overcurrent
detection signal
Output overcurrent
detection delay time
)8-37
)unction Code Parameter Name Setting Range Default
)8-38 Any current reaching 1 0.0%–300.0% (rated motor current) 100.0%
)8-39
Any current reaching 1
amplitude
0.0%–300.0% (rated motor current) 0.0%
)8-40 Any current reaching 2 0.0%–300.0% (rated motor current) 100.0%
)8-41
Any current reaching 2
amplitude
0.0%–300.0% (rated motor current) 0.0%
If the output current of the AC drive is within the positive and negative amplitudes of any
current reaching detection value, the corresponding DO becomes ON.
The MD380 provides two groups of any current reaching detection parameters, including
FXUUHQWGHWHFWLRQYDOXHDQGGHWHFWLRQDPSOLWXGHVDVVKRZQLQWKHIROORZLQJ¿JXUH