Description of Function Codes
MD380 User Manual
- 204 -
)unction Code Parameter Name Setting Range Default
)9-49
)ault protection
action selection 3
Unit's digit (User-de¿ned fault 1, Err27)
00000
Same as unit's digit in )9-47
Te
n's digit (User-de¿ned fault 2, Err28)
Same as unit's digit in )9-47
Hundred's digit (Accumulative power-on time
reached, Err29)
Same as unit's digit in )9-47
Thousand's digit (Load becoming 0, Err30)
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run at 7% of rated motor frequency
and resume to the set frequency if the load
recovers
Te
n thousand's digit (PID feedback lost during
running, Err31)
Same as unit's digit in )9-47
)9-50
)ault protection
action selection 4
Unit's digit (To
o large speed deviation, Err42)
00000
Same as unit's digit in )9-47
Te
n's digit (Motor over-speed, Err43)
Same as unit's digit in )9-47
Hundred's digit (Initial position fault, Err51)
Same as unit's digit in )9-47
Thousand's digit (Speed feedback fault, Err52)
Same as unit's digit in )9-47
Te
n thousand's digit: Reserved
If "Coast to stop" is selected, the AC drive displays Err** and directly stops.
If "Stop according to the stop mode" is selected, the AC drive displays A** and stops
according to the stop mode. After stop, the AC drive displays Err**.
If "Continue to run" is selected, the AC drive continues to run and displays A**. The
UXQQLQJIUHTXHQF\LVVHWLQ)
)unction Code Parameter Name Setting Range Default
)9-54
)requency selection
for continuing to run
upon fault
0: Current running frequency
1: Set frequency
2: )requency upper limit
3: )requency lower limit
4: %ackup frequency upon abnormality
0
)9-55
%ackup frequency
upon abnormality
0.0%–100.0% (maximum frequency) 100.0%