MD380 User Manual Desc
ription of Function Codes
- 225 -
)unction Code Parameter Name Setting Range Default
A1-03 VDI4 function selection 0–59 0
A1-04 VDI5 function selection 0–59 0
VDI1 to VDI5 have the same functions as DI terminals on the control board and can be used
IRUGLJLWDOLQSXW)RUPRUHGHWDLOVVHHGHVFULSWLRQRI)WR)
)unction Code Parameter Name Setting Range Default
A1-05 VDI state setting mode
Unit's digit (VDI1)
00000
0: Decided by state of VDOx
1: Decided by A
1-06
Te
n's digit (VDI2)
0, 1 (same as VDI1)
Hundred's digit (VDI3)
0, 1 (same as VDI1)
Thousand's digit (VDI4)
0, 1 (same as VDI1)
Te
n thousand's digit (VDI5)
0, 1 (same as VDI1)
A1-06 VDI state selection
Unit's digit (VDI1)
00000
0: Invalid
1: Va
lid
Ten's digit (VDI2)
0, 1 (same as VDI1)
Hundred's digit (VDI3)
0, 1 (same as VDI1)
Thousand's digit (VDI4)
0, 1 (same as VDI1)
Te
n thousand's digit (VDI5)
0, 1 (same as VDI1)
Different from DI terminals, VDI state can be set in two modes, selected in A1-05:
 Decided by state of VDOx
Whether the state a VDI is valid is determined by the state of the corresponding VDO
DQG9',[LVXQLTXHO\ERXQGWR9'2[[LVEHWZHHQDQG)RUH[DPSOHWRLPSOHPHQW
the function that the AC drive reports an alarm and stops when the AI1 input exceeds
the limit, perform the following setting:
1) Allocate VDI1 with function 44 "User-de¿ned fault 1" (A1-00 = 44).
2) Set A1-05 to xxx0.
3) Allocate VDO1 with function 31 "AI1 input limit exceeded" (A1-11 = 31).
efesotomasyon.com