MD380 User Manual Desc
ription of Function Codes
- 241 -
)unction Code Parameter Name Display Range
U0-03 Output voltage 0–11
40 V
It displays the AC drive's output voltage in the running state.
)unction Code Parameter Name Display Range
U0-04 Output current
0.00–655.35 A (AC drive power 55 kW)
0.0–6553.5 A
(AC drive power ! 55 kW)
It displays the AC drive's output current in the running state.
)unction Code Name Display Range
U0-05 Output power 0–32767
It displays the AC drive's output power in the running state.
)unction Code Parameter Name Display Range
U0-06 Output torque -200.0%–200.0%
It displays the AC drive's output torque in the running state.
)unction Code Parameter Name Display Range
U0-07 DI state 0–32767
It displays the current state of DI terminals. After the value is converted into a binary number,
each bit corresponds to a DI. "1" indicates high level signal, and "0" indicates low level signal.
The corresponding relationship between bits and DIs is described in the following table.
%it0 %it1 %it2 %it3 %it4 %it5 %it6 %it7 %it8 %it9
DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10
%it10 %it11 %it12 %it13 %it10 %it11 %it12 %it13 %it14 %it15
VDI1 VDI2 VDI3 VDI4 VDI1 VDI2 VDI3 VDI4 VDI5
)unction Code Parameter Name Display Range
U0-08 DO state 0–1023
It indicates the current state of DO terminals. After the value is converted into a binary
number, each bit corresponds to a DO. "1" indicates high level signal, and "0" indicates
low level signal. The corresponding relationship between bits and DOs is described in the
following table.
Table 6-15 Corresponding relationship between bits and DOs
%it0 %it1 %it2 %it3 %it4 %it5
DO3 Relay 1 Relay 2 DO1 DO2 VDO1
%it6 %it7 %it8 %it9 %it10 %it11
VDO2 VDO3 VDO4 VDO5