EasyManua.ls Logo

Inovance MD380-5T5.5GB - Page 35

Inovance MD380-5T5.5GB
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mechanical and Electrical Installation MD380 User Manual
- 34 -
)LJXUH(PEHGGHGLQVWDOODWLRQRIWKH0'VKHHWPHWDOKRXVLQJ
Install the AC drive from the
back of the control cabinet .
%DFNSDQHORI
control cabinet
)LJXUH(PEHGGHGLQVWDOODWLRQHIIHFWRIWKH0'VKHHWPHWDOKRXVLQJ
Ƶ
Installation Precautions
1) Reserve the installation clearances as specified in )igure 3-1 to ensure sufficient
space for heat dissipation. Take heat dissipation of other parts in the cabinet into
consideration.
2) Install the AC drives upright to facilitate heat dissipation. If multiple AC drives are
installed in the cabinet, install them side by side. If one row of AC drives need to be
installed above another row, install an insulation guide plate, as shown in )igure 3-2.
3) Use incombustible hanging bracket.
4) In scenarios with heavy metal powder, install the heatsink outside the cabinet, and
ensure that the room inside the fully-sealed cabinet is as large as possible.