Mechanical and Electrical Installation MD380 User Manual
- 40 -
Type Terminal Name
)XQFWLRQ'HVFULSWLRQ
Analog input
AI1-GND Analog input 1
Input voltage range: 0–10 VDC
,PSHGDQFHNȍ
AI2-GND Analog input 2
Input range: 0–10 VDC/4–20 mA, decided by
jumper J8 on the control board
,PSHGDQFHNȍYROWDJHLQSXWȍFXUUHQW
input)
Digital input
DI1- OP Digital input 1
Optical coupling isolation, compatible with dual
polarity input
,PSHGDQFHNȍ
Voltage range for level input: 9–30 V
DI2- OP Digital input 2
DI3- OP Digital input 3
DI4- OP Digital input 4
DI5- OP
High-speed pulse
input
%HVLGHVIHDWXUHVRI',±',LWFDQEHXVHGIRU
high-speed pulse input.
Maximum input frequency: 100 kHz
Analog
output
AO1-GND Analog output 1
Voltage or current output is decided by jumper J5.
Output voltage range: 0–10 V
Output current range: 0–20 mA
Digital output
DO1-CME Digital output 1
Optical coupling isolation, dual polarity open
collector output
Output voltage range: 0–24 V
Output current range: 0–50 mA
Note that CME and COM are internally insulated,
but they are shorted by jumper externally. In this
case DO1 is driven by +24 V by default. If you
want to drive DO1 by external power supply,
remove the jumper.
)M- COM
High-speed pulse
output
,WLVOLPLWHGE\))0WHUPLQDORXWSXWPRGH
selection).
As high-speed pulse output, the maximum
frequency hits 100 kHz.
$VRSHQFROOHFWRURXWSXWLWVVSHFL¿FDWLRQLVWKH
same as that of DO1
Relay output
T/A-T/% NC terminal
Contact driving capacity:
250 VAC, 3 A, COSø = 0.4
30 VDC, 1 A
Applying to Overvoltage Category II circuit
T/A-T/C NO terminal
Auxiliary interface
J12
Extension card
interface
I28-pin terminal
Connect to an optional card (I/O extension card,
PLC card and various bus cards)
J3 PG card interface
Support various types of PG cards: OC,
differential, UVW and resolver.
J7
External operation
panel interface
Connect to external operation panel.