Options
‑124‑
Figure 5‑38 AC output reactor model
Note
● The following recommended AC output reactors are applicable only to T1 to T9
models.
● For T10 to T12 models, if AC output reactors are required, purchase the AC output
reactors with the model name containing "‑L".
● The T13 model is equipped with a built‑in output reactor as standard.
Table 5–46 Selection of Inovance AC output reactors (three‑phase 380 V to 480 V)
Structure Drive Model Reactor Model Inductance (mH) Loss (W)
T1 MD520‑4T0.4B(S) MD‑OCL‑5‑1.4‑4T‑1% 1.4 ‑
MD520‑4T0.7B(S) MD‑OCL‑5‑1.4‑4T‑1% 1.4 ‑
MD520‑4T1.1B(S) MD‑OCL‑5‑1.4‑4T‑1% 1.4 ‑
MD520‑4T1.5B(S) MD‑OCL‑5‑1.4‑4T‑1% 1.4 ‑
MD520‑4T2.2B(S) MD‑OCL‑7‑1.0‑4T‑1% 1.0 ‑
MD520‑4T3.0B(S) MD‑OCL‑10‑0.7‑4T‑1% 0.7 ‑
T2 MD520‑4T3.7B(S) MD‑OCL‑10‑0.7‑4T‑1% 0.7 ‑
MD520‑4T5.5B(S) MD‑OCL‑15‑0.47‑4T‑1% 0.47 ‑
T3 MD520‑4T7.5B(S) MD‑OCL‑20‑0.35‑4T‑1% 0.35 ‑
MD520‑4T11B(S) MD‑OCL‑30‑0.23‑4T‑1% 0.23 ‑
T4 MD520‑4T15B(S) MD‑OCL‑40‑0.18‑4T‑1% 0.18 ‑
T5 MD520‑4T18.5(B)(S)
MD520‑4T18.5(B)(S)‑T
MD‑OCL‑40‑0.18‑4T‑1% 0.18 ‑
MD520‑4T22(B)(S)
MD520‑4T22(B)(S)‑T
MD‑OCL‑50‑0.14‑4T‑1% 0.14 ‑
T6 MD520‑4T30(B) (S) MD‑OCL‑60‑0.12‑4T‑1% 0.12 ‑
MD520‑4T37(B) (S) MD‑OCL‑80‑0.087‑4T‑1% 0.087 ‑
T7 MD520‑4T45(B) (S) MD‑OCL‑90‑0.078‑4T‑1% 0.078 ‑
MD520‑4T55(B) (S) MD‑OCL‑120‑0.058‑4T‑1% 0.058 ‑