Wiring
‑52‑
Terminal layout
● Pin may of the input connector
Terminal
Pin No.
Name
Value
Description
CN6
1 COM 0 V
STO reference
ground
2 24 V 24 V
Internal 24V
power supply
3 STO1
‑
Control input for
STO2
4 STO2
‑
Control input for
STO1
● Two isolated inputs are configured to dual‑channel inputs of the STO function:
STO1/STO2.
● To facilitate commissioning, additional pin with supply voltage (+24V) is
integrated. The bridging of the 24 V terminal to STO1/STO2 is needed in case the
safety circuit is installed but no STO function is needed.
Note
If you need STO, you must remove the short circuit jumper.