Intercall 600/700 Installation & Operation Guide Issue 4.27 Page 21 of 78
First Fix.
Please read the advice given on page 17 with regard to power supply position and required cabling techniques.
INTERCALL 600 and 700 Mains connection requirements
L617 600 Series Master Power Supply
Non Switched Fused Spur unit with 5amp fuse fitted
L717 700 Series Master Power Supply
Non Switched Fused Spur unit with 5amp fuse fitted
L737 600/700 Series Booster Power Supply
Non Switched Fused Spur unit with 5amp fuse fitted
L748 600/700 Corridor LED Display
Non Switched Fused Spur unit with 5amp fuse fitted
RFTX Scope pager transmitter
Non Switched Fused Spur unit with 5amp fuse fitted
DPU414 Thermal Printer
Standard 13amp socket
Due to the wide variety of
fixing possibilities, the Intercall system is not supplied with backboxes. We recommend the
following available from your local electrical wholesaler or supplier.
SURFACE MOUNTING: INTERCALL BB1 BACKBOX
FLUSH MOUNTING: 35mm Depth DOUBLE METAL
BOXES
SURFACE MOUNTING: CRABTREE 9047 or
CONTACTUM 1042 FLUSH MOUNTING: 25mm Depth
SINGLE METAL BOXES*
L628 600 SERIES DISPLAY UNIT L622 / L722 NON AUDIO CALL POINTS
L752 700 SERIES AUDIO CALL POINT L746 600/700 SERIES OVERDOOR LIGHTS
L758 700 SERIES AUDIO LCD DISPLAY UNIT L714 600/700 SERIES REMOTE SOUNDER
L762 700 SERIES AUDIO CALL/DISPLAY UNIT RX1 RADIO RECEIVER
FJB2 600 / 700 SERIES PROTECTED JUNCTION BOARD RB1 RELAY BOARD
L747(MK2) 600 / 700 SERIES UNIVERSAL INTERFACE PIR1 PASSIVE INFRA RED DETECTOR
VERY IMPORTANT
DO NOT USE METAL BACKBOXES BOXES WITH FOUR MOUNTING LUGS AS THEY RESTRICT ACCESS
AND CAN DAMAGE SOME UNITS.
INTERCALL 600 and 700 Equipment which is not mounted in backboxes
L617 600 Series Master Power Supply
Wall Mounted W240 x H180 x D100
(Allow 200mm access on all sides)
L717 700 Series Master Power Supply
Wall Mounted W240 x H180 x D100
(Allow 200mm access on all sides)
L737 600/700 Series Booster Power Supply
Wall Mounted W240 x H180 x D100
(Allow 200mm access on all sides)
TP1 Tone Pager Kit
Desk Mounted – Requires no fixed installation
RFTX Scope Transmitter Kit
Wall Mounted W190 H330 D100 (Not including aerial)
(Allow 200mm Access around all sides)
CS1 Ceiling Pull Switch
Surface mounting only - Requires no backbox
DPU414 Thermal Printer
Desk Mounted – Requires no fixed installation