Intercall 600/700 Installation & Operation Guide Issue 4.27 Page 29 of 78
L717 Intelligent Power Supply Unit.
The L717 may be used with Intercall 700 & Intercall 600 systems provided all network devices were manufactured
after August 2003. The L617 600 Series Power Supply is still available for maintaining earlier Intercall 600
systems as you cannot replace the L617 with a L717 without ensuring all network devices are 600/700
compatible. The L717 provides power and data signals for the network devices and stores the text programming
information & when this is customised, it will need to be downloaded to any new display, call logger or pager interface
installed on the system at a later date. When using with an Intercall 700 with Intercom, the (A) and (B) cables do
not connect to this unit.
Mains Terminals: 220-240VAC @ 20W (Max)
Battery Leads: 12v, 1.9/2.1/2.4 Ah sealed lead acid battery. OBSERVE POLARITY!
Output Terminals (+-): Three pairs provided for convenience, connect to network devices.
LIM Connector: Connects to LIM for system text programming. (See page52)
Configuration Switches: See page 73 for a complete list of DIL switch settings.
Day/Night Terminals: By connecting a switch between these two terminals you can switch the
between the two volume levels set-up on the displays. (See Pages 35)
Download Button: Press & hold for 10 seconds, then release, to download text to LCD displays.
THE BATTERY MUST BE CONNECTED WHEN DOWNLOADING
Reset Pins: If shorted, resets the power supply and cancels all calls active on the system.
Mains Failure Alarm: Beeps every 3 seconds when no mains supply is present.
Red Led: Flashes, indicating unit is operating correctly.
Yellow Led: Indicates AC is present and transformer is operating.
Green Led: Indicates 12volt DC supply is present and fuse is intact
Onboard Fuse: 1Amp 20mm protection for power supply & battery.
Installation: Self Contained Surface Mounted Case. (See Below)
Size & Weights: 225 x 180 x 90 mm, 1400g
Intercall 600
617/717
Intercall 700
717
+
-
+
-
+
-
E L N
Mains Supply
failure alarm
Battery Leads – Red (+) Black (-)
Battery Fuse
1 Am
p
20m
m
Reset Pins
Network Output
terminals
Day/Night Switch
Terminals
Supply 220~240v AC
Connect to Fuse Spur with
3A fuse fitted
DO NOT CONNECT TO
PLUG TOP
Red micro LED
Green DC LED
Yellow AC LED
12345678
ON DIP
Download Button
LIM Programming
Connector
configuration
switches