Intercall 600/700 Installation & Operation Guide Issue 4.27 Page 32 of 78
L622AN310 Call Point with Extended Inputs & Outputs.
The L622AN310 is a modification of the standard L622 unit with additional terminals to provide an emergency call
generation for WC or en-suit bathroom ceiling pull switches and L2/X3 terminals for SRP connection. (As per L722)
Operation of the unit is identical to the L622 Standard Unit. It can generate up to 6 independent levels of call which are
indicated by the integral twin colour re-assurance LED. There is a ‘call follower’ sounder which sounds when the call
point is in ‘staff present’ mode to inform staff of another call. The jack socket will accept any closing contact input
from pear leads, pressure mats, radio triggers and a host of other triggering devices. The X and L terminals are used to
connect to ceiling pull switches. Options which must be specified when ordering include; magnetic key reset,
(L622MAN121) Please refer to page 9 for a guide on the use of the call point. For Non-Latching applications, please
see the L634 on page 45.
Network Terminals: Connect to the Intercall 600 (2 wire) Network. [+, –] OBSERVE POLARITY
X Terminal: Connect external normally open contacts between here and Network –ve to trigger the call
point into standard call.
X2 Terminal: Connect external normally open contacts between here and Network –ve to trigger the call
point into emergency call from the En-suit or Bathroom.
Re-assurance LED: Slow Red flashing – Standard Call
Slow Red/Green flashing – Assistance Call
Rapid Red flashing – Emergency/Crash Call
Green flashing - Accepted Call – Staff on their way
Constant Green – Nurse Present Mode
L Terminal: Red LED Output for ceiling pull switches with built in re-assurance lights.
L2 Terminal: Green LED Output for SRP (Slave Reset Points).
Pear lead Socket: Industry standard socket that will accept any normally open switch.
This socket can accept input from pear leads, pressure mats, radio triggers etc.
Installation: Flush or surface mount in standard ‘single size’ electrical backbox.
Size & Weights: 80 x 80 x 40 mm, 70g
Plug-on connector for
Network and Ceiling
Pull Switch.
Staff Present ‘Call
follower’ sounder
Address switches set the
uni