Intercall 600/700 Installation & Operation Guide Issue 4.27 Page 73 of 78
L617 / L717 Configuration Switch Settings
The global system features are controlled by a bank of DIL
switches fitted to the L617 and L717 Power Supplies. The
switches are shown to the right and [ON] is upwards
(towards the word ON) and [OFF] is down (away from the
word ON). The tables below details the available settings.
L617 Power Supply CONFIGURATION SWITCH SETTINGS
SW3 SW4 Time taken for an accepted call to return to the calling condition
ON ON 30 Seconds
ON OFF 1 Minute
OFF ON 2 Minutes
OFF OFF
2 Minutes and 30 Seconds * [Do not use these settings simultaneously]
SW5 SW6 Time taken for an un-answered call to convert to an emergency call
ON ON Never convert to an emergency call
ON OFF
2 Minutes and 30 Seconds * [Do not use these settings simultaneously]
OFF ON 3 Minutes and 30 Seconds
OFF OFF 6 Minutes and 30 Seconds
SW SWITCH ON SWITCH OFF
SW1
Enable Staff Present feature Disable Staff Present feature
SW2
Disable Call Follower Sounder Enable Call Follower Sounder
SW7
Not used
SW8
Not used
* Do not use these settings simultaneously
L717 Power Supply CONFIGURATION SWITCH SETTINGS
SW3 SW4 SW5
Time for Accepted calls to
return to their calling state
Time for an un-answered call
to become a Priority call
ON ON ON 1 Minute & 30 Seconds 2 Minutes & 30 Seconds
OFF ON ON 2 Minutes 3 Minutes & 30 Seconds
ON OFF ON 3 Minutes 2 Minutes & 30 Seconds
OFF OFF ON 4 Minutes 2 Minutes & 30 Seconds
ON ON OFF 1 Minute & 30 Seconds 6 Minutes & 30 Seconds
OFF ON OFF 2 Minutes Never turn into a Priority call
ON OFF OFF 3 Minutes 3 Minutes & 30 Seconds
OFF OFF OFF 4 Minutes Never turn into a Priority call
SW SWITCH ON SWITCH OFF
SW1
Manual staff present feature only
[Reset Button Present/Reset toggle]
Automatic Staff Present Feature only**
[Reset Button Reset only]
SW2
Disable call point follower sounder Enable call point follower sounder
SW6
No lost addresses logged by displays lost addresses logged on displays
SW7
Show location + User ID on system User ID disabled
SW8
Disable Nurse Present Auto Expiry
Timer [Fixed at 10 minutes]
Enable Preset Auto Expiry Timer
[Manual Reset Only]
L747SL SERIAL RS232 LEAD FOR SCOPE PAGERS, CMS LITE &
PROGRAMMING L747
L747 25 way female Connector Description PC 9 way female Connector
Pin 13 CTS <<< Pin 4+7
Pin 14 TXD >>> Pin 2
Pin 15 RXD <<< Pin 3
Pin 17 RTS >>> Pin 6+8
Pin 25 Signal Ground Pin 5
YOU WILL NEED TO USE THE SOFTWARE IF CHANGING THE PAGER ADDRESS