Intercall 600/700 Installation & Operation Guide Issue 4.27 Page 33 of 78
L733 Door Monitoring & Access Control Point.
The L733 replaces the L722DK as the Door Monitoring Point for the Intercall 600 and Intercall 700 systems. It is used
to protect fire doors, entrance & exit doors or other sensitive areas. The door is fitted with a magnetic contact (not
supplied), which is used to trigger the call point and activate the call system. The unit is controlled with the use of a key
token, which performs all functions when brought near the token detection area on the facia. The unit features standard
call and emergency call generation, integral 20 second exit timer with audible bleep and mode jumper to prevent
sensitive or dangerous exit doors being permanently left open. In mode I & II, the unit automatically re-arms when the
door is closed. In mode III, the unit must be manually re-armed. The unit is supplied with one magnetic token.
Network: Connect to the Intercall 600 or 700 (2 wire) Network. [+, –] OBSERVE POLARITY
X Terminal: Standard Call Input, if the unit goes into alarm it will generate a standard call.
X2 Terminal: Emergency Call Input, if the unit goes into alarm it will generate an emergency call.
X3 Terminal: Remote authorised access press button input, this mimics the functions of the token area in a
remote location (eg external side of the door)
Exit Timer: To allow authorised personnel to use the door without generating an alarm. Before opening the
door, swipe the token area once, the green LED will flash and the sounder will pulse. The door
may now be opened, however, if the door remains open after the 20 seconds, the alarm will sound.
If the door is opened & shut within 20 seconds, the unit will re-arm immediately.
JP1 Fitted: Mode I: This allows the door to be permanently left open. Before opening the door, swipe the
token area twice, the sounder stops & the LED is continuously green. The door can now be
opened and left open without an alarm being generated. Once the door is shut, the unit will
automatically re-arm immediately.
JP1 Removed: Mode II: This prevents the door from being permanently left open & disables the double swipe
feature.
LK1 Cut: Mode III: This removes the exit timer and converts the single swipe into on/off mode. Before
opening the door, swipe once to isolate the door & the green LED will light. Opening and closing
the door while isolated has no effect. Close the door and swipe to re-arm the unit.
Alarm Reset: The alarm is reset but closing the door and swiping the token area once.
Installation: Flush or surface mount in standard ‘single size’ electrical back-box.
Size & Weights: 80 x 80 x 40 mm, 70g