Intercall 600/700 Installation & Operation Guide Issue 4.27 Page 59 of 78
L628 Display Menu Settings Only
Access to the display menus is obtained by first pressing and holding down the ‘Show Staff’ button. While holding
down the ‘Show Staff’ button, press & hold the ‘Accept Call’ button down for 10 seconds*. To change the displayed
option, press the ‘Show Staff’ button. To move to the next item, press the ‘Accept Call’ button. When the display is
showing the last menu item one more press of the ‘Accept Call’ will return the unit to normal operating mode.
* This unit is fitted with a jumper which must be fitted to allow access to the menu.
Menu Settings Description
DISPLAY ADDRESS:
00
00 to 07 or 15
Sets the Display Address of the unit. When display address 1 or
above is selected, and the unit is not in master mode, the menu will
jump to 2ND TONE LO ADD.
ZONE A LOW ADD:
001
001 to 215
Select the Lowest call point address for zone switch position A. This
function is available only when the display is in master mode or set to
Display Address 00.
ZONE A HI ADD:
215
001 to 215
Select the Highest call point address for zone switch position A. This
function is available only when the display is in master mode or set to
Display Address 00.
ZONE B LOW ADD:
001
001 to 215
Select the Lowest call point address for zone switch position B. This
function is available only when the display is in master mode or set to
Display Address 00.
ZONE B HI ADD:
215
001 to 215
Select the Highest call point address for zone switch position B. This
function is available only when the display is in master mode or set to
Display Address 00.
ZONE C LOW ADD:
001
001 to 215
Select the Lowest call point address for zone switch position C. This
function is available only when the display is in master mode or set to
Display Address 00.
ZONE C HI ADD:
215
001 to 215
Select the Highest call point address for zone switch position C. This
function is available only when the display is in master mode or set to
Display Address 00.
2ND TONE LOW ADD:
OFF
OFF / 001 to 215
Select the Lowest call point address for the Second Tone alarm
setting. This range operates in addition to the zone windows above.
2ND TONE LOW ADD:
OFF
OFF / 001 to 215
Select the Highest call point address for the Second Tone alarm
setting. This range operates in addition to the zone windows above.
ACCEPT BUTTON:
ENABLED
ENABLED
DISABLED
When enabled, allows the calls to be accepted at this display using the
Accept button. When disabled, this function does not operate on this
display only.
SHOW ALL CALLS:
ENABLED
ENABLED
DISABLED
When enabled, this display will show all calls on the system but will
only sound the audible alarm for calls in the current zone.
SOUND FOR:
ALL CALLS
ALL CALLS
EMERGENCY CALLS
ONLY
Select “Emergency Only” to allow Emergency and Attack calls only
to generate the audible alarm from this display. All other call types
will be shown but the audible alarm will not operate on this display.
ACCEPT ATTACK:
ENABLED
ENABLED
DISABLED
When enabled, allows ATTACK calls to be accepted at this display
using the Accept button. When disabled, this feature will be removed
from this display only.
PRIORITY CALLS:
ALL ZONES
OWN ZONE ONLY
ALL ZONES
Select “All Zones” to allow this display to show and sound for Priority
calls in all zones on the system. “Own Zone Only” will not show or
sound for Priority Calls from other zones.
EMERGENCY CALLS:
ALL ZONES
OWN ZONE ONLY
ALL ZONES
Select “All Zones” to allow this display to show and sound for
Emergency and Attack calls in all zones on the system. “Own Zone
Only” will not show or sound for Emergencies or Attack calls from
other zones.