Intercall 600/700 Installation & Operation Guide Issue 4.27 Page 67 of 78
Zoning – Example 3.
In the example below, we have 2 zones with 8 call points, 2 display units and one remote sounder on each zone. There
is a zone switch in each zone which controls the displays in the local zone only. There are two modes of operation; 1.
LCD Displays and Remote Sounders show/sound for calls within their own zone only, and 2. Show calls /sound for
calls from zone 1 and 2 on the local displays and sounders.
Call Points.
• Call points are set up with consecutive addresses in each zone, with a gap between zones as per example 1.
LCD Displays.
• Set up the master display in zone 1 as follows:
• DISPLAY ADDRESS 01. We wish all displays in zone 1 to be switched together, but not affect the displays in the
other zones. As we are using display address 1 the address window settings can only be set on the master display
and all other displays, and remote sounders, set to display address 1 will pick up the settings.
• Set: ZONE A LOW ADD 1,ZONE A HIGH ADD 8. The first address window ‘Zone A’ is set to receive only
local calls from zone 1.
• Set: ZONE B LOW ADD 1,ZONE B HIGH ADD 22. The second address window ‘Zone B’ is set to receive calls
from both zone 1 and zone 2.
• Set: ZONE C LOW ADD 215,ZONE C HIGH ADD 215. The second address window is set up away from any
call point address (at address 215) so when using the ‘Zone B’ setting, the displays will not respond to any call.
• Set the Remote Sounder to display address 01. The remote sounders will pick up the address window settings
which are entered into the master display set to display address 1 in zone 1.
• Set up the master display in zone 2 as follows:
• DISPLAY ADDRESS 02. We wish all displays in zone 2 to be switched together, but not affect the displays in
zone 1.
• Set: ZONE A LOW ADD 15,ZONE A HIGH ADD 22. The first address window ‘Zone A’ is set to receive only
local calls from zone 2. As we are using display address 2 the address window settings can only be set on the
master display and all other displays, and remote sounders, set to display address 2 will pick up the settings.
• Set: ZONE B LOW ADD 1,ZONE B HIGH ADD 22. The second address window ‘Zone B’ is set to receive calls
from both zone 1 and zone 2.
• Set the Remote Sounder to display address 02. The remote sounders will pick up the address window settings
which are entered into the master display set to display address 2 in zone 2.
Zone Switches.
• Connect a zone switch in each zone to select either ‘Address Window A’ or ‘Address Window B’. When the zone
switch is operated, it will select the address windows for all displays in the local zone only. It will not affect
displays in the other zone. For information on the connections for the zone switch, please refer to page 35
If you do not wish to switch the zone setting but you wish to use Remote Sounders, fit links to the master displays in
zone 1 and zone 2 to permanently select ‘Address window A’ and enter the settings into the master displays.
1 01 2 3 4 5 6 7 01 801
15 16 17 18 19
20 21 02 22
02 02
Zone 1
Zone 2