EasyManua.ls Logo

Interlogix SB Series - Operating Modes

Interlogix SB Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
When the detectors are placed one on the top of the other (see Figure 9 below),
allocate the same channel to each detector and relay them to each other by the
synchronization link in Column mode.
Figure 9: Single channel example
(1)
(1)
(2) (2
)
(1) Channel 1 (2) Inter-module connection
Operating modes
The SB450-N and SB4100-N barriers can operate in 2 modes:
“AND” mode: simultaneous obscuration of 2 dual-beam cells to trigger the
intrusion alarm.
“OR” mode: obscuration of one of the dual-beam cells to trigger the intrusion
alarm.
The mode is selected with DIP switches 3 to 5. The DIP switch location is shown
in Figure 5 on page 6.
See Figure 10 on page 12 for modes illustration and DIP switch settings.
Caution: The DIP switches settings must be identical on both of 2 associated
modules. In OR mode, the response time must be also equal.
SB Series AIR Beam Detectors In
stallation Manual 11

Related product manuals