DRY mode operation procedure
If room Temp is more than 2℃ below Set TEMP. , compressor and outdoor unit fan motor stop,
indoor unit fan motor runs at low speed.
If room Temp is between 2℃ of Set TEMP, the compressor and outdoor unit fan motor will run for
6 minutes and stop for 4 minutes, and always in such a cycle, the indoor unit fan motor will run at low
speed.
If room Temp is more than 2℃ above Set TEMP. , compressor and outdoor unit fan motor run as
COOL mode , the indoor unit fan motor runs at low speed.