What to do if Invertek Drives Inverter trips on overload?
- KKatelyn AndersonAug 23, 2025
If your Invertek Drives Inverter trips on overload, check to see when the decimal points are flashing (drive in overload) and either increase acceleration rate or reduce the load. Also, check that the motor cable length is within specification. Ensure the motor nameplate parameters are correctly entered (P1-07, P1-08, and P1-09). If operating in Vector mode (P4-01 – 0 or 1), also check the motor power factor in P4-05. Ensure an autotune has been successfully completed for the connected motor. Finally, check the load mechanically to ensure it is free, and no jams, blockages or other mechanical faults exist.