Optidrive Compact-2 Engineering Guide Issue 07.docx
32
www.invertekdrives.com
8
Control Terminal Connections
8.3.4. Macro Functions - User PI Control Mode (P-12 = 5 or 6)
P-15
DI1
DI2
DI3 / AI2
DI4 / AI1
Diagram
0
1
0
1
0
1
0
1
0
STOP
ENABLE
PI REF
P-20 REF
Analog Input AI2
Analog Input AI1
4
1
STOP
ENABLE
PI REF
AI1 REF
Analog Input AI2 (PI FB)
Analog Input AI1
4
3, 7
STOP
ENABLE
PI REF
P-20
E-TRIP
(NC)
Analog Input AI1 (PI FB)
3
4
(NO)
START
(NC)
STOP
Analog Input AI2 (PI FB)
Analog Input AI1
12
5
(NO)
START
(NC)
STOP
PI REF
P-20 REF
Analog Input AI1 (PI FB)
5
6
(NO)
START
(NC)
STOP
E-TRIP
(NC)
Analog Input AI1 (PI FB)
8
STOP
RUN
FWD
REV
Analog Input AI2 (PI FB)
Analog Input AI1
4
14
STOP
RUN
-
-
E-TRIP
(NC)
Analog Input AI1 (PI FB)
16
15
STOP
RUN
P-23 REF
PI REF
Fire Mode
Analog Input AI1 (PI FB)
1
16
STOP
RUN
P-23 REF
P-21 REF
Fire Mode
Analog Input AI1 (PI FB)
1
17
STOP
RUN
P-21 REF
P-23 REF
Fire Mode
Analog Input AI1 (PI FB)
1
18
STOP
RUN
AI1 REF
PI REF
Fire Mode
Analog Input AI1
1
2,9,10,11,12,13 = 0
For information on the External Trip (E-TRIP) and motor thermistor monitoring function, see section 6.7 Motor Thermistor Connection.
Fire Mode input logic (Normally Open or Normally Closed) and latching mode are selected by P-30. When the input mode is set to latched,
the enable signal must be removed to reset the latch.