motor parameters on the
name plate.
To guarantee the control
performance, configure the
motor as the standard motor.
If the motor power has a
great gap between the
standard, the control
performance of the inverter
will decrease obviously.
Note: Resetting the motor
rated power (P02.15) will
initialize P02.16~P02.19.
After motor parameter
autotuning, the settings of
P02.20~P02.22 update
automatically. As basic
parameters for high
performance vector control,
the parameters have a direct
impact on the control
performance.
When P00.15=1 (rotation
autotuning), in no need of
change, P02.23 will update
via autotuning; when
P00.15=2 (static autotuning),
P02.23 cannot update via
autotuning, so calculate the
value and update it by
manual.