0:No protection
1: Common motor (with low speed compensation)
Because the heat-releasing effect of the common
motors will be weakened, the corresponding electric
heat protection will be adjusted properly. The low
speed compensation characteristic mentioned here
means reducing the threshold of the overload
protection of the motor whose running frequency is
below 30Hz.
2: Variable frequency motor (without low speed
compensation)
Because the heat-releasing effect of the specific
motors will not be impacted by rotation speed, there
is no need to adjust the protection value during
low-speed running.
Times of motor overload M=Iout/(In*K)
In is the rated current of the motor, Iout is the output
current of the inverter and K is the motor overload