Goodrive300-01 inverter for air compressor Function parameters
-57-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
1: Only / keys adjustment is valid
2: Only digital potentiometer adjustment is valid
3: Neither / keys nor digital potentiometer
adjustment is valid
LED tens: frequency control selection
0: Only valid when P00.06=0 or P00.07=0
1: Valid for all frequency setting manners
2: Invalid for multi-step speed when multi-step speed
has the priority
LED hundreds: action selection during stopping
0: Setting is valid
1: Valid during running, cleared after stopping
2: Valid during running, cleared after receiving the
stop command
LED thousands: / keys and digital
potentiometer integral function
0: The integral function is valid
1: The integral function is invalid
P08.43
Integral ratio of
the keypad
potentiometer
0.01~10.00s
0.10s
P08.44
UP/DOWN
terminals control
0x000~0x221
LED ones: frequency enable selection
0: UP/DOWN terminals setting valid
1: UP/DOWN terminals setting invalid
LED tens: frequency control selection
0: Only valid when P00.06=0 or P00.07=0
1: All frequency manners are valid
2: When the multi-step has the priority, it is invalid to
the multi-step speed.
LED hundreds: action selection during stopping
0: Setting is valid
1: Valid during running, cleared after stopping
2: Valid during running, cleared after receiving the
stop command
0x000
P08.45
UP terminals
frequency
changing ratio
0.01~50.00Hz/s
0.50 Hz/s
P08.46
DOWN terminals
0.01~50.00Hz/s
0.50 Hz/s