0x00~0x11
LED ones:
0: Keep on integral adjustment when the frequency
reaches the upper and low limit; the integration
shows the change between the reference and
feedback unless it reaches the internal integral limit.
When the trend between the reference and feedback
changes, it needs more time to offset the impact of
continuous working and the integration will change
with the trend.
1: Stop integral adjustment when the frequency
reaches the upper and low limit. If the integration
keeps stable and the trend between the reference
and feedback changes, the integration will change
with the trend quickly.
LED tens:
0: The same with the setting direction; if the output of
PID adjustment is different from the current running
direction, the internal will output 0 forcedly.
1: Opposite to the setting direction; if the output of
PID adjustment is different from the current running
direction, conduct the output of close loop
adjustment which is opposite to the current running
direction.