Goodrive300-01 inverter for air compressor Function parameters
-63-
Detailed instruction of parameters
0: Input phase loss protection disabled
1: Input phase loss protection enabled
LED tens:
0: Output phase loss protection disabled
1: Output phase loss protection enabled
LED hundreds:
0: Input phase loss hardware protection disabled
1: Input phase loss hardware protection enabled
Frequency
decreasing at
sudden power
loss
Frequency
decreasing ratio
at sudden power
loss
Setting range: 0.00Hz/s~P00.03 (Max. output
frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency decreasing point and
the inverter begins to decrease the running
frequency at P11.02 to make the inverter generate
power again. The returning power can maintain the
bus voltage to ensure a rated running of the inverter
until the recovery of power.
Frequency
decreasing threshold
Note:
1. Adjust the parameter properly to avoid the
stopping caused by inverter protection during
the switching of the grid.
2. Disable input phase loss protection to enable
this function.
Overvoltage stall
protection