Goodrive300-01 inverter for air compressor Function parameters
-65-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
Setting range of P11.06: 50.0~200.0%
Setting range of P11.07: 0.00~50.00Hz/s
P11.08
Overload
pre-alarm of
motor/inverter
The output current of the inverter or the motor is
above P11.09 and the lasting time is beyond P11.10,
overload pre-alarm will be output.
Setting range of P11.08:
Enable and define the overload pre-alarm of the
inverter or the motor.
Setting range: 0x000~0x131
LED ones:
0: Overload pre-alarm of the motor, relative to the
rated current of the motor
1: Overload pre-alarm of the inverter, relative to the
rated current of the inverter
LED tens:
0: The inverter continues to work after overload and
underload pre-alarm
1: The inverter continues to work after underload
pre-alarm and it stops running after overload fault
2: The inverter continues to work after overload
pre-alarm and it stops running after underload fault
3: The inverter stops running after overload and
underload pre-alarm
LED hundreds :
0: Detection all the time
1: Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~3600.0s
0x000
P11.09
Overload
pre-alarm
detection level
150%
P11.10
Overload
pre-alarm
detection time
1.0s
P11.11
Underload
pre-alarm
If the inverter or motor output current is lower than
P11.11, and its lasting time is beyond P11.12, the
50%