Goodrive300-01 inverter for air compressor Function parameters
-70-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
current of SM2
P12.26
Motor 2 overload
protection
0:No protection
1: Common motor (with low speed compensation)
2: Variable frequency motor (without low speed
compensation)
2
P12.27
Motor 2 overload
protection
coefficient
Times of motor overload M=Iout/(In*K)
In is the rated current of the motor, Iout is the output
current of the inverter and K is the motor overload
protection coefficient.
So, the smaller the value of K is, the bigger the value
of M is. When M=116%, the fault will be reported
after 1 hour; when M=200%, the fault will be reported
after 1 minute; when M>=400%, the fault will be
reported instantly.
The setting range: 20.0%~120.0%
100.0%
P12.28
Correction
coefficient of
motor 2 power
Correct the power displaying of motor 2.
Only impact the displaying value other than the
control performance of the inverter.
The setting range: 0.00~3.00
1.00
P12.29
Parameter display
of motor 2
0: Display according to the motor type; in the mode,
only display the related parameters of current motor
type for the convenience of operation
1: Display all; in the mode, display all motor
parameters
0
P13 Group Synchronous motor control
P13.00
Reduction
coefficient of
source current
0.0~100.0%
80.0%
P13.01
Original pole test
mode
0: No test
1: High-frequency superposition (reserved)
2: Pulse superposition
0